Note: This is a general guideline spec. Many States have unique energy
code compliance requirements. Additionally, many States have Modular
Building State approval requirements that alter these specifications
to meet all State codes. Mainly energy code upgrades. We urge you to
consult with a professional knowledgeable Sales Person at B.I.G. for
assistance.
PART 1 – GENERAL
================
1.01 SUMMARY
Provide all labor, equipment and materials to furnish one
prefabricated steel Attendant Booth.
1.02 Related work specified elsewhere
A. Electrical service supply and connection.
B. Site/foundation work.
C. Unloading, placement, installation and anchoring.
D. Plumbing & piping (if required).
1.3 Submittals
A.
Upon award of order, manufacturer shall prepare and submit shop
drawings for each different building required for this project.
Drawings shall include elevations, section, floor plan, electric
schedule, service entrance locations, and anchor clip detail.
1.4 Quality assurance
A.
Structures shall be the product of a manufacturer with a minimum
of 20 years-documented experience in the design and fabrication of
portable steel buildings.
B.
Prefabricated buildings by manufacturers other than the one
approved shall submit sufficient data to enable approval to be
given. As a minimum: design drawings and/or calculations,
applicable certifications, catalog information, and color samples
showing equal range of variety.
C.
Design loads: Live Loads: Per requirements for the installation
location. Unit to be manufactured to be in full compliance with
the State Codes and State certification where applicable.
PART 2 - PRODUCTS
=================
2.1 MANUFACTURERS
A.
Products of the following manufacturer from the basis for design
and quality intended.
1. B.I.G. Enterprises, Inc. South El Monte CA. 800-669-1449.
B. Or equal as approved in accordance with Section 01600 for
Substitutions.
2.
Structure
A.
Prefabricated steel building shall be single unit welded
construction. Building to be shipped completely assembled. All
welded joints ground smooth. Base Dimensions to be __’ x __’ x __
tall.
B. 2" x 2" x .083” cold drawn electro-welded structural mechanical
steel frames.
2.
WALLS
A. 16ga. Galvanized steel interior and exterior panels MIG welded
between frame and mullions for self-aligning unitized system, creating
a structural diaphragm. Booth to have an exterior continuous layer of
R-10 insulation encapsulated within the final exterior layer of
galvanized steel panels.
2.
Base and floor
A. Unit to have a 12ga. Galvanized steel plate floor welded to a 2” x
2” perimeter galvanized steel tube frame with structural joists welded
to the frame. Floor deck to be covered with black polyvinyl chloride
commercial resilient textured 1\4” x 20” x 20” inter locking tiles and
4" high black base cove. Floor to have four interior steel anchor
plates welded to the floor frame with interior removable access panel
above each anchor clip. No exterior anchor clips allowed.
2.
Door
A. Unit to have one (or specify two) commercial steel framed 3’0” x
6’8” sliding door top hung by eight 2 1\4” rigid steel ball bearing
rollers with a lower stainless steel guide, stainless steel pull
handles welded to the frame and mortise lock.
Windows
A. 16ga. galvanized steel window frame system with flush mounted
corners and welded fastening. Unit to have fixed windows on all sides.
All windows glazed with 1\4” tinted tempered glass.
Recommended glazing upgrade: All windows glazed with 3\4” tinted
tempered dual pane insulating glass.
2.
Roof
A.
Roof to be standard design for interior or exterior use. Roof to
be constructed of internal steel framing with 16-gauge galvanized
steel roof deck that has a three part membrane with a SRI index of
95 or better. Roof to have a 8” fascia with 3” overhang on all
sides. Roof to drain to downspouts from the rear overhang soffit.
All booths 6’ x 8’ or larger have removable lifting rings for
hoisting by crane.
2.
counter
A. Booth to have a 20” deep painted galvanized steel shelf at the
front end wall mounted at 34” AFF.
2.
Electrical
A.
Load Center shall be 125 Amp rated, 120/240 volt, single phase, 3
wire 12 pole panel mounted in a location in full compliance with
National Electric Code (NEC). Two 20 amp duplex outlets mounted
under the front shelf, interior LED light(s) recessed in a 16ga.
painted galvanized steel ceiling and controlled by a wall mounted
switch.
B.
Air conditioner to be a through the rear wall mounted unit with
12,000 BTU cooling and 11,200 BTU heating with dedicated 230 volt
outlet.
WEATHER PROOFING
A. Weather-tight for exterior use. All seams and joints pressure
bonderized. All openings fully weather stripped, roof coated as
specified..
B. Rust inhibitive high build epoxy primer and two part polyurethane
finish coat. Paint to have minimum 3500 hour salt sprat test. Booth to
be painted one color inside and out as selected ted by Architect.
PART 3 - EXECUTION
==================
1.
General
A. Install prefabricated buildings on flat and level concrete pad in
accordance with the manufacturer's recommendations and placement
drawings. Position units over utility stub-ups, verify building is
level and anchor.
2.
INSTALLATION
A. Units shall be shipped fully assembled, fully wired, fully glazed
and thoroughly painted.
A.
Position units over electrical stub-up on level pad. Drill and set
expansion type anchor bolts.
B.
Connect power and seal around edges where the floor base meets the
concrete pad.
END OF SECTION